The wrong generator for a hurricane is usually not the one that is too small. It is the one bought by the wattage on the box, fed from three gas cans that ran dry on day two, and parked in the carport because the rain was coming in. Sizing is a method, not a product: add up what you actually need to run, work out how much fuel that burns per day, then decide whether an inverter generator, a tri-fuel unit or a battery station delivers it best.
Every wattage below is a typical value from a manufacturer’s chart and only a starting point. The number that counts is on your own appliance’s nameplate, and for anything with a motor the starting surge on the decal beats any chart. This is one page of the hurricane preparedness hub; the engine-versus-battery decision itself is the backup power pillar.
Step One: List the Loads
Write down what you want running at the same time during the outage, not everything in the house. A Gulf Coast hurricane outage has a short list: the refrigerator and freezer, one window air conditioner or at least a bedroom fan, a well pump if you are on a well, any medical device (a CPAP, an oxygen concentrator, refrigerated medication), phone and radio charging, a few lights, and a microwave or coffee maker used for minutes at a time. Our hurricane power outage checklist walks that priority list.
Step Two: Running Watts and Starting Watts
Champion’s wattage chart defines the two numbers. Running watts are the steady power a device needs after it has started. Starting watts are the extra power some devices need to turn on, which Champion says may be estimated at one to two times the running watts. Anything with a compressor or motor has a surge; a light, a charger or a television does not.
| Load | Running watts (typical) | Starting watts (typical) | Note |
|---|---|---|---|
| Refrigerator | 400 | 2,200 | Champion chart; the compressor cycles, so the surge repeats all day |
| Chest or upright freezer | not published | not published | Nameplate; a compressor load like the refrigerator |
| Window air conditioner | 1,200 | 2,000 | Champion chart; larger BTU units draw more |
| Well pump | not published | not published | Motor load with a large surge; use the pump’s nameplate |
| CPAP (ResMed AirSense 11 with humidifier and heated tube) | 56 | 73 peak | ResMed user guide: typical 56.1 W, peak 73.2 W; other models differ |
| Other medical devices | not published | not published | Nameplate; ask the supplier for the surge |
| Box or pedestal fan | not published | not published | Small motor; read the label |
| Phone and tablet chargers | not published | none | Printed on each charging brick; count every brick in use |
| LED television | 80 | none | Champion chart |
| Desktop computer | 100 | none | Champion chart; a laptop charger is lower |
| Desk lamp | 40 | none | Champion chart lists 40 running; Champion’s sizing guide says light bulbs need only running watts |
| Microwave | 800 | 2,000 | Champion chart; minutes at a time |
| Coffee maker | 800 | none | Champion chart |
Two cautions. The refrigerator figure is a typical modern unit; an older side-by-side with an ice maker can sit well above it. And a freezer is not free: with both, you have two compressors that can start within seconds of each other.
Step Three: Add Them Up, Then Add a Margin
Champion’s method is the standard one. Total the running watts of every item that will be on at once, then add the single highest starting figure to that total. The first number must sit under the generator’s rated running watts, the second under its rated starting watts. The method assumes one motor starts at a time, which is why a house with a refrigerator, a freezer and a window unit should either stagger the starts by hand or size for two surges.
Then add a margin. We suggest keeping the running total at no more than about 75 to 80 percent of the rated running watts. That is our editorial rule, not a manufacturer figure, and it exists because engines lose output in heat and humidity, cords lose some of what the generator makes, and running near the ceiling leaves no room before an overload, which OSHA warns can lead to overheating and a fire hazard.
Step Four: Fuel Per Day
Manufacturers publish runtime at a stated load, and the arithmetic is tank size divided by hours. Champion rates its 4500-watt dual fuel inverter at 14 hours on a 2.25-gallon tank at 25 percent load: about 0.16 gallons an hour, roughly 3.9 gallons for a continuous day and 1.9 for a 12-hour day. On propane it is rated at 21 hours on a 20-pound cylinder at 25 percent load, a bit more than one cylinder a day continuous and about half on a 12-hour schedule. Those are 25 percent figures; at the half load a refrigerator plus a window unit represents, fuel goes faster, and Champion publishes no 50 percent runtime for this model, so measure your own on the first day.
Firman’s manual for the T09275 tri-fuel publishes propane consumption at half load of 3.2 liters an hour (77,500 BTU an hour). That is about 0.85 gallons an hour, roughly 20 gallons for a continuous day and 10 for a 12-hour day. Ferrellgas puts a 20-pound cylinder at up to 4.7 gallons when full, so a half-load 12-hour day on this generator is a little over two grill cylinders and a continuous day more than four. On gasoline the T09275 carries a 9-gallon tank; the manual’s specification table publishes no gasoline runtime, so take that from the product page or your own first day. Natural gas, where the house has it, removes the storage problem entirely, which is the strongest argument for the tri-fuel class.
Storage and refueling have rules that do not bend. Gasoline goes in approved, labeled containers outside living areas, per the NFPA tip sheet, and Ready.gov keeps the fuel, like the generator, outdoors and at least 20 feet from windows, doors and attached garages. Treat it with stabilizer and do not carry it into the next season; Firman’s manual says both. Refuel only with the engine off and cool: Firman specifies at least two minutes of cooling before the cap comes off, and the NFPA’s wording is never while it is hot. Propane sidesteps most of this; it does not go stale, and the only rules are upright, outdoors and out of the exhaust path.
Step Five: Match the Number to a Class
| Class | Representative unit | Rated output (manufacturer) | Fuel | Fits a household that |
|---|---|---|---|---|
| Inverter generator | Champion 4500W dual fuel | 4,500 starting / 3,500 running on gasoline; 4,500 / 3,150 on propane | Gasoline or 20 lb propane cylinders | Needs the refrigerator, lights, charging, a CPAP and one window unit, with the microwave managed |
| Tri-fuel open frame | Firman T09275 | 11,400 / 9,200 on gasoline; 10,400 / 8,300 on propane; 8,650 / 6,900 on natural gas; 120/240V, 50A outlet | Gasoline, propane or natural gas | Needs a well pump, two cooling loads, a freezer and a transfer switch into the panel |
| Battery station | Anker SOLIX F3000 | 3,600 W output; about 3 kWh, expandable to 12 kWh; 2,400 W solar input; 20 ms switchover | Wall, solar or a generator | Wants silent overnight power for the refrigerator, medical devices and fans, recharged by day |
The inverter class is the answer for most houses not on a well: 3,500 running watts covers a refrigerator, a window unit, lights and charging, and the propane option means fuel that does not go stale, stored upright outdoors and away from the house as NFPA and the manufacturer direct, never in the garage. The tri-fuel class is for the house with a well pump or a 240-volt load, where 9,200 running watts and a 50-amp outlet into a transfer switch make the generator a substitute for the utility. The battery class changed the calculation: a station like the F3000, or the Jackery HomePower 3000 and EcoFlow DELTA 3 Classic we also review, runs the quiet loads overnight with no fuel or exhaust and recharges from solar or from the generator while it runs anyway; our solar generator roundup compares the field. The combination to aim for is a generator sized for the daytime loads and a battery sized for the night.
Three Example Households
| Household | Loads on at once | Running watts (chart) | Starting watts (chart) | Class |
|---|---|---|---|---|
| A: couple, no well, one CPAP | Refrigerator, CPAP, LED TV, laptop, one lamp | about 680 | about 2,900 | Inverter generator, or a battery station alone for the night |
| B: family of four, one window unit | Refrigerator, window air conditioner, CPAP, TV, computer, two lamps; microwave only between compressor starts | about 1,900 (about 2,700 with the microwave on) | about 4,100 (about 4,900 with the microwave on) | Inverter generator with the microwave managed; a tri-fuel unit removes the juggling |
| C: on a well, two cooling loads, a freezer | Refrigerator, freezer, well pump, two window units, lights, charging, a medical device | chart loads plus the freezer and pump nameplates | two motor surges likely to overlap | Tri-fuel into a transfer switch, plus a battery for the overnight loads |
Household B is the one that catches people: the running total fits an inverter generator, but the starting total only fits if the microwave is off when a compressor starts. The tri-fuel class buys the freedom not to think about it, at the cost of fuel.
Carbon Monoxide: Where the Generator Goes
The sizing is worthless if the generator ends up in the garage, so the placement rules go here. The CDC’s instruction is to operate a generator outdoors, more than 20 feet from windows, doors and vents, and never inside a home or garage even with the doors and windows open. The NFPA tip sheet gives the same 20 feet from all doors, windows and vent openings and names the attached garage with the door up as a place it must never run. Firman’s manual, typical of the manufacturers, adds downwind with the exhaust pointed away, at least 5 feet from any structure or vegetation, and never under a deck.
Then put a battery-powered carbon monoxide alarm in the house; the CDC requires one whenever a generator runs, and a hardwired alarm without a battery is silent in the outage. Our Kidde battery CO alarm review covers the one we recommend. The shut-off built into current generators (Champion’s CO Shield, Firman’s CO Alert) stops the engine when exhaust pools around it, but Firman’s own manual states that it does not replace a CO alarm in the home. Both, always. The CDC lists the symptoms as headache, dizziness, weakness, upset stomach, vomiting, chest pain and confusion; if anyone has them while a generator is running, get everyone to fresh air and call for help. Our generator safety guide covers placement, rain and refueling in depth.
Transfer Switch, Interlock Kit or Extension Cords
There are three legitimate ways to get generator power into a house. The first is a transfer switch, which the NFPA says should be properly rated under the National Electrical Code and installed by a qualified electrician; Firman’s manual says licensed electrician and explains why: the switch isolates the generator from the utility so it cannot energize the wires a line crew is working on. The second is a listed interlock kit on the main panel, fed through an outdoor generator inlet box; Champion describes the interlock as a mechanical device that keeps the main utility breaker and the generator breaker from being on at the same time. Check local code and permit rules, and have a licensed electrician install it. The third is extension cords from the generator to individual appliances, sized to the load. Firman’s table for cords up to 50 feet: 16 gauge to 13 amps, 14 gauge to 15 amps, 12 gauge to 20 amps, 10 gauge to 30 amps, 6 gauge for 50 amps. The same manual says cords run through a door or window are not recommended, because every opening a cord holds ajar is a path for exhaust.
Never connect a generator to the house wiring through a dryer outlet or any wall receptacle with a double-ended cord, a practice called backfeeding. With nothing isolating the house from the utility, OSHA warns that it can energize wiring systems for great distances, creating a risk of electrocution for utility workers and others in the area, and Champion warns it can severely damage the home’s electrical system. Do not do it, do not let a neighbor talk you into it, and if a transfer switch or interlock kit is in the budget this year, have it installed before June.
Common Questions
What size generator runs a refrigerator and a window air conditioner?
On Champion’s chart, a refrigerator at 400 running and 2,200 starting watts plus a window unit at 1,200 and 2,000 gives 1,600 running and about 3,800 starting watts if one compressor starts at a time. A 3,500 running, 4,500 starting inverter generator covers that with lights and charging added, provided the microwave is not run during a compressor start. Read both nameplates before trusting the chart.
How much gasoline should I store for a week?
Work it from the manufacturer’s runtime. Champion’s 4500-watt inverter at 25 percent load burns about 1.9 gallons in a 12-hour day, roughly 14 gallons for a week of half-days and more at higher load. Store it in approved, labeled containers outside living areas, treated with stabilizer, and do not keep it into the next season. Propane and natural gas are the ways around the storage problem.
Can I run a CPAP from a generator?
Yes, and an inverter generator or a battery station is the better source because of the cleaner output. ResMed’s AirSense 11 user guide lists typical consumption of 56.1 watts and a peak of 73.2 watts with the humidifier and heated tube, small enough that a battery station covers a full night with no engine running.
Bottom Line
List the loads that will run at once, take the running watts from the nameplates (the chart figures above are placeholders), add the single largest starting surge, and size the generator so the running total sits around three-quarters of its rating. Do the fuel math from the manufacturer’s runtime and be honest about what a week of gallons or cylinders means. Most houses without a well land on an inverter generator plus a battery station for the night; houses with a well or 240-volt loads land on a tri-fuel unit into a transfer switch. Whatever you buy runs outdoors more than 20 feet from any opening with a battery CO alarm inside, is refueled cold, and is never connected through a wall outlet. The day-by-day use of that power is in 72 hours without power, the engine-versus-battery decision in the backup power pillar, and the rest of the season in the hurricane preparedness hub.
Updated 2026-11-01: replaced a misprinted desk-lamp starting figure, added listed interlock kits as a connection method and corrected the backfeeding explanation against OSHA, NFPA and Champion.